KRAUS & NAIMER Control Switches up to 25 A

39 Technical Data CG, CH, CHR Switches Selection Data CH6 CHR6 CG4 CG6 CH10 CHR10 CH16 CHR16 CG4-1 CG8 CH10B CHR10B CH16B CHR16B Nm Ib-in A A A A A A A A A A A A A A A A A A A A Tightening torque of screws DC Switching Capacity1 Kontakte in Serie: 1 2 3 4 5 6 8 Permissible voltage in volts Utilization category 24 48 72 96 120 144 192 DC-21A, DC-21B 48 96 144 192 240 288 384 Switching of resistive load 60 120 180 240 300 360 480 Time constant L/R≤1ms 110 220 330 440 550 660 – 220 440 660 – – – – Utilization category 24 48 72 96 120 144 192 DC-22A, DC-22B 48 96 144 192 240 288 384 Switching of mixed resistive 60 120 180 240 300 360 480 and inductive load 110 220 330 440 550 660 – f.e. shunt motors 220 440 660 – – – – Time constant L/R≤2,5ms Utilization category 24 48 72 96 120 144 192 DC-23A, DC-23B 48 96 144 192 240 288 384 Switching of highly 60 120 180 240 300 360 480 inductive loads 110 220 330 440 550 660 – f.e. series motors 220 440 660 – – – – Time constant L/R≤15ms Utilization category 24 48 – – – – – DC-13 48 96 – – – – – Control of electromagnets 60 120 – – – – – Time constant L/R≤100ms 110 220 – – – – – 220 440 – – – – – Rated Thermal Current Ie 1Values for switches with spring return on request. 0,4 0,8 1,2 1,4 1,2 1,4 3,5 7 10 12 10 12 10 16 16 16 21 21 6 14 14 14 18 18 5 13 13 13 17 17 4 6 6 6 6 6 0,8 0,9 0,9 0,9 1 1 8 14 14 14 18 18 5 13 13 13 17 17 4 12 12 12 16 16 1,5 1,9 1,9 1,9 2 2 0,3 0,3 0,3 0,3 0,3 0,3 7 13 13 13 16 16 4 12 12 12 15 15 3,5 10 10 10 14 14 1 1,5 1,5 1,5 1,7 1,7 0,2 0,2 0,2 0,2 0,2 0,2 0,8 3 3 3 – – 0,5 1,7 1,7 1,7 – – 0,2 1,4 1,4 1,4 – – – 0,7 0,7 0,7 – – – 0,15 0,15 0,15 – – < back to table of contents >