User Manual 9 < back to the table of contents > 4.3 Installation 4.3.1 Installing the DAT.PM.063A3P.KA The DAT.PM.063A3P.KA can be installed before and/or after a Kraus & Naimer main switch KA40 or KA63. The module can be configured for threephase or single-phase operation. For more information, refer to Chapter 7.5 Edit Configuration. Figure 6 shows the installation for the 3-pole connection before the switch. For installation after the switch, the same wires and tightening torque are used as for the installation before the switch. Table 4 contains all technical requirements for wire connection. Figure 6: Installation of the DAT.PM.063A3P.KA Module (3-pole) 4.3.2 Installation of the DAT.PM.063A3P.KA – Single-Phase Operation For single-phase installation, the neutral conductor must always be connected to terminal X2 of the DAT.PM.063A3P.KA. The phase conductor can be connected to either terminal X1 or X3, depending on the desired wiring layout. Further configuration options, such as the connection type and energy flow direction, are explained in Chapter 7.5 Edit Configuration. Table 4: Wire Specifications Conductor construction Min. Max. Stripping length Max. outer diameter wire stranded 4 mm² / AWG 12 16 mm² / AWG 6 15 mm² / AWG 0.59 in 9.2 mm² / AWG 3.62 in solid/multi-wired 2.5 mm² / AWG 14 25 mm² / AWG 4 stranded with ferrule 16 mm² / AWG 6 stranded with insulated ferrule Info! When connecting the single-phase version, the neutral conductor must always be connected to terminal X2! The phase conductor can be connected to either terminal X1 or X3. The connection type (single-phase or three-phase) and the energy flow direction must be configured in the web portal. 1 2 3 PH2 Anzugsdrehmoment/ Mountig torque: 2 [Nm]/ 18 [Ib-in]