COM/DAT User Manual

User Manual 37 < back to the table of contents > Table 12 shows the storage durations of the ‘Direct’ and ‘Averaged’ databases depending on the number of DAT-Modules, based on the default setting of 2 seconds. Table 12: Data storage duration for different numbers of DAT-Modules at a data update interval of 2 seconds Resolution 1 DAT 10 DAT 16 DAT 32 DAT 2 s 145 h 14 h 9 h 4 h 5 m 910 d 91 d 57 d 28 d 30 m 5461 d 546 d 341 d 170 d 3 h 32768 d 3277 d 2048 d 1024 d 12 h 131072 d 13107 d 8192 d 4096 d As shown in Table 13, the storage duration changes only for the direct database when the data update rate is adjusted. The procedure for changing the data update rate is described in Chapter 7.7 Expert Mode. Table 13: Data storage duration for different numbers of DAT-Modules at a data update interval of 500 ms Resolution 1 DAT 10 DAT 16 DAT 32 DAT 500 ms 36 h 3 h 2 h 1 h 5 m 910 d 91 d 57 d 28 d 30 m 5461 d 546 d 341 d 170 d 3 h 32768 d 3277 d 2048 d 1024 d 12 h 131072 d 13107 d 8192 d 4096 d

RkJQdWJsaXNoZXIy MTAxNzE=