103 Technical Information Technical Information KN10 - 1 OR 3 PHASE REVERSING SWITCH kVA to Amps Connection Guides M1 M2 M3 5 7 1 M 1 3 5 Single Phase 6 10 2 Three Phase L1 L2 L3 2 4 6 10 Note: Fit Loop 1 - 5 Run Start P N 4 5.77 6.08 5 7.22 7.60 6 8.66 9.12 7 10.10 10.64 8 11.55 12.16 10 14.43 15.19 12 17.32 18.23 15 21.65 22.79 20 28.87 30.39 25 36.09 37.98 30 43.30 45.58 40 57.74 60.78 50 72.17 75.97 60 86.61 91.16 70 101.04 106.36 80 115.47 121.55 90 129.91 136.74 100 144.34 151.94 110 158.78 167.13 120 173.21 182.33 150 216.51 227.91 160 230.95 243.10 180 259.82 273.49 200 288.68 303.88 250 360.85 379.85 300 433.03 455.82 350 505.20 531.79 400 577.37 607.75 4 17.30 18.31 5 21.40 22.88 6 26.09 27.46 7 30.43 32.04 8 34.78 36.61 10 43.48 45.77 12 52.17 54.92 15 65.22 68.65 20 86.96 91.43 25 108.70 114.42 30 130.43 137.30 40 173.91 183.07 50 217.39 228.83 60 260.87 274.60 70 304.35 320.37 80 347.83 366.13 UNITY power Factor 1.0 UNITY power Factor 1.0 Three Phase 400V Single Phase 230V power Factor .95 power Factor .95 KVA KVA Amps = 1000 x kVA / Line Volts x 1.732 x eff x pf
RkJQdWJsaXNoZXIy MTAxNzE=