Control and Load Switches for higher Capacities CAD, CA and C type up to 315 A L type up to 2400 A Catalog 100 10 / 2024
Kraus & Naimer The development of the Blue Line rotary switch and motor starter product ranges is based on more than hundred years experience by Kraus & Naimer in the design and manufacture of electrical switchgear. Kraus & Naimer pioneered the introduction of the cam operated rotary switch and continues to be recognized as the world leader in that product field. BLUE LINE Blue Line products are protected by numerous patents through-out the industrial world. They are built to national and international standards and designed to withstand adverse temperatures and climates. Blue Line products are accepted and universally recognized for their quality and workmanship. They are supported by a worldwide sales and service organization. The Kraus & Naimer Registered Trademark WORLDWIDE SYMBOL FOR QUALITY SWITCHGEAR
Disconnectors and Main Switches acc. to IEC 60947-3 see Catalog 500 Contents Page Construction Data 4 Dimensions and Nominal Ratings 5 How to order 6, 7 Switch Function and Configuration C, CA and CAD Switches 10 A-315 A ON/OFF Switches 9 Double-throw Switches 10-12 General Application Switches 12 Coding Switches 13 Multi-step Switches 14-16 Voltmeter Switches 17-18 Ammeter Switches 19-21 Volt-ammeter Switches 21 Control Switches 21, 22 Motor Switches 23-25 L Switches 350 A-2400 A ON/OFF Switches 26, 27 Double-throw Switches 28, 29 Multi-step Switches 30-32 Types of Mounting Panel Mounting 33-37 Base Mounting 38 Wall Mounting 39 Face Plates 40, 41 Handles 42 International Standards and Approvals 43 Technical Data 44-48 Dimensions Panel Mounting 49-53 Base Mounting 53, 54 Wall Mounting 55 Overall Switch Lengths 55, 56 Blue Line Switchgear: Summary 58
4 Construction Data The load switches of the C, CA and CAD-series offer a solution for most cam switch applications. Different contact designs, contact materials and terminals allow for their use as control switches, instrumentation switches and motor control switches, as well as in electronic circuitry and in aggressive environments according to IEC 60947-3 and VDE 0660 part 107. The stage is the basis for all switches and can be supplied with a maximum of 2 contacts. The terminals are accessible from the side. CA and CAD switches are supplied with open terminals to facilitate wiring and are protected against accidental finger contact according to EN 50274, VDE 0660 part 514 and DGUV V3. Switches up to type CA25B are supplied with captive screws with clamping plates. The switch types CA40-CA63 are supplied with box terminals. Captive plus-minus terminal screws and integrated screwdriver guides facilitate wiring. If a positive manual operation or a higher DC rating is required, many of these switches can be fitted with a snap action latching mechanism - suffix „S“ - to the switch type. The cam-operated switches of the L-series are continuous current rated for off-load switching. They may be used to switch resistive or low inductive loads. Special Contact Systems CA4/CA4-1 CAD4-1/CAD11/CAD12 High contact reliability by multiple cross-point contacts, electronic compatible. High contact reliability by H-bridge design with “cross-wire“ contacts. The contact system with gold-plated contacts (CAD12 with silver contact) allows for low voltages, electronic compatible. Type CA4, CA4-1, CAD4-1 CA10-CA25 CA10S-CA25S CAD11, CAD12 CA10B-CA25B C26, C32, C42 C26S, C32S, C42S CA40, CA50, CA63 C43, C80, C125, C200-4 C315 L350, L351, L630, L631 L1000 L400, L600, L800, L1200, L1600, L2000 S00 S0 S0 S0 S1 S1 S1 S1 S2 S3 S2 S3 9 12 on request 12 12 12 on request 12 12 12 12 12 30°, 45°, 60°, 90° 30°, 45°, 60°, 90° 60°, 90° 30°, 45°, 60°, 90° 30°, 45°, 60°, 90° 20°, 30°, 45°, 60°, 90° 60° 30°, 45°, 60°, 90° 20°, 30°, 45°, 60°, 90° 30°, 45°, 60°, 90° 30°, 45°, 60°, 90° 30°, 45°, 60°, 90° Size Possible Switching Angles Max. No. of Stages Above illustrates the standard terminal positions. L Switches C Switches CA and CAD Switches (CA4-CA25B) CA Switches (CA40-CA63) Latching mechanism determines the switch positon 20,30,45,60,90 Degree Four-hole mounting. . . . . . . . ........ E or single -hole mounting 22 mm dia . .. FT or base mount. . . . . . . . . . .......... VE or DIN rail mounting. . . . . . . ....... VE1 Stages Up to 12 Face Plate Handle Frame Shaft < back to table of contents >
5 Nominal Ratings 1Valid for lines with grounded common neutral termination, overvoltage category III, pollution degree 3. Values for other supply systems on request. 2Ambient temperature 35 °C max. 3Additional switch functions on request. S00 S0 S1 S2 S3 Insulation Voltage1 Ui V 440 440 440 690 690 690 690 600 600 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 1000 690 690 690 690 690 690 Thermal Current Iu/Ith A 10 10 5 20 20 25 32 6 6 20 20 25 32 32 50 63 40 50 63 63 115 150 200 350 350 6302 6302 10002 315 315 500 8002 11002 14502 19002 24002 Motor Rating 3 x 380 V-440 V AC-23 AC-3 kW kW 3 2,2 3 2,2 - - 7,5 5,5 7,5 5,5 11 7,5 15 11 - - - - 7,5 5,5 7,5 5,5 11 7,5 15 11 15 11 22 15 30 18,5 18,5 15 22 18,5 30 18,5 30 18,5 45 30 75 37 75 37 90 37 90 37 90 37 90 37 90 37 132 55 132 55 132 55 132 55 132 55 132 55 132 55 132 55 Switch Size Type CA4 CA4-1 CAD4-1 CA10 CA11 CA20 CA25 CAD11 CAD12 CA10B CA11B CA20B CA25B C26 C32 C42 CA40 CA50 CA63 C43 C80 C125 C200-4 L350 L351 L630 L631 L1000 C315 C3163 L400 L600 L800 L1200 L1600 L2000 According to IEC 60947-3/VDE 0660 part 107 For further technical details, refer to pages 44-47. To furnish with gold contacts and quick connects see page 6. < back to table of contents >
6 1Technical data on request. 2Additional length for switches with B, C, S, amendments refer page 54. How to order Disconnectors and Main Switches according to IEC 60947-3 see Catalog 500 Three types of data (shown below) are required for ordering Blue Line cam-operated switches. Code numbers for ordering are shown in this catalog. 1. Type of Switch The type of switch required may be easily selected by referring to the table on page 5 which shows the thermal current, power rating and dimensions of each switch. For further technical details, refer to pages 44-47. Variations of contacts and terminals are shown below. 2. Switch Function The code numbers for standard switches shown on pages 8-32 indicate the switch function, face plate, handle and any optional extras. Additional coding to modify type and color of handle and face plate is explained below. 3. Type of Mounting Types of mounting are shown on pages 33-39. Catalog 101 describes enclosures and optional extras. Specify the mounting code to indicate required mounting. CA10 A202 VE Handles, Face Plates and Optional Extras The handles for standard switches shown on pages 8-32 are suitable for mounting units with four hole mounting. Alternative types of handles available are illustrated on page 42, and mounting units on pages 31-37. When a handle, face plate or optional extra is required but not covered by the dash number, the code number for the selected component should be entered separately. A comprehensive range of available standard face plates is illustrated on pages 40 and 41. Non-standard or special face plate engravings are available at extra cost. The large number of optional extras and enclosures is covered in Catalog 101. Switch Size Blue Line switches are available in sizes S00, S0, S1, S2 and S3. These size codes indicate the dimensions of the mounting, the face plate and the handle, as well as the size of optional devices and enclosures. Page 5 lists these sizes and the various switch types they include. Type of Switch Extending the switch type coding the following combinations will define: Amendment Definition For switch types -1 with gold contacts1 CA4-1, CA4N-1, CA10-1, CA11-1, CA10B-1, CA11B-1, CAD4-1 -4 with quick connects CA4-4 B2 S0 switches with latching mechanism size S1 CA10B, CA11B, CA25B, CAD11B, CAD12B C2 S1 switches with latching mechanism size S2 CA40C, CA50C, CA63C L with lockout-relay w/o manual release for std. sw. CA10L, CA25L, C26L M with lockout-relay with manual release for std. sw. CA10M, CA25M, C26M, C42M X with power failure release CA10X, CA20X, CA25X, C26X, C32X, C42X Y with power failure release and trip-free release CA10Y, CA20Y, CA25Y S2 with snap action CA10S, CA20S, CA25S with 60° or 90° switching C26S, C32S, C42S, CA40S, CA50S, CA63S with 60° switching R with spring return latching mechanism CA10R, CA25R, CAD11R, CAD12R Example: Coding for switch type CA10 with gold contacts is CA10-1. < back to table of contents >
7 How to order Ordering of Special Switches and Face Plates When ordering special switches and face plates it is advisable to use our order form, as illustrated. The customer’s requirements are shown in blue as an example. For technical reasons, it may not be possible to follow the sequence of contacts requested by the customer. The final contact development which is sent with every switch will show the customer’s original terminal markings. CA20 1 2 3 4 5 7 9 x G001 VE M004 /02 1A 0 60 MOTOR 1 O H A O H A R K S x x xx x xx x x x Order forms are available on request. < back to table of contents >
Notes: 8 < back to table of contents >
Code Type/Handle CA4 CAD.. CA40 CA4-1 CA10- CA10B- C26CAD4-1 CA25 CA25B C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram 9 1for use in a three phase four-wire system with switched neutral 2not available for switch type CA25 3not available for switch type C315 WAA100 WAA101 WAA102 WAA103 A204 A205 WAA206 WAA207 A290 A291 A292 A324 A293 WAA327 WAA325 A326 WAA208 A200 A201 A202 A203 WAA653 WAA341 A342 A343 A344 WAA654 WAA345 A346 WAA347 A348 ON/OFF Switches with 60° Switching ON/OFF Switches with 90° Switching 1 pole contacts 2 pole preclose 30° 3 pole 4 pole 4 pole 1 pole preclose 60°1 4 pole 3 pole preclose 30° 5 pole contacts 6 pole preclose 30° 3 pole 360° rotation 1 1 2 2 2 2 3 3 2 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I ON/OFF Switches with 30° Switching 1 pole 2 pole 3 pole 4 pole 1 pole with spring return 2 pole with spring return 3 pole with spring return 4 pole with spring return 1 1 2 2 1 1 2 2 I I I I I I I I I I I I2 I I I I I3 I3 I3 1 pole 2 pole 3 pole 4 pole 4 pole 1 pole preclose 6°1 5 pole 6 pole 7 pole 8 pole 8 pole 2 pole preclose 6°1 9 pole 10 pole 11 pole 12 pole 1 1 2 2 2 3 3 4 4 4 5 5 6 6 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I K K 1-4 pole 1-4 pole F070 F056 F062 1, 2, 3, 4, 5 and 6 pole 4 pole 1 pole preclose 6° 8 pole 2 pole preclose 6° 1-12 pole F169 F153 4 pole 1 pole preclose 60° 4 pole 3 pole preclose 30° < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA40 CA4-1 CA10- CA10B- C26CAD4-1 CA25 CA25B C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA120 WAA121 WAA122 WAA123 A295 A296 WAA297 A720 A721 A722 A723 WAA973 A795 A220 A221 A222 A223 WAA673 A369 A370 A371 A372 WAA972 WAA373 WAA374 WAA375 WAA376 10 Double-throw Switches without „OFF“ 60° Switching 1not available for switch type CA25 2for use in a three phase four-wire system with switched neutral 1 pole 2 pole 3 pole 4 pole 4 pole 1 pole preclose 6°2 5 pole 6 pole 7 pole 8 pole 8 pole 2 pole preclose 6°2 9 pole 10 pole 11 pole 12 pole Double-throw Switches without „OFF“ with electrically isolated contacts Double-throw Switches without „OFF“ 30° Switching 1 2 3 4 4 5 6 7 8 8 9 10 11 12 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 1 pole 2 pole 3 pole 4 pole 4 pole 1 pole preclose 6°2 1 pole with spring return 1 2 3 4 4 1 I I I I I I I I I I I I I I I I I I I I I I I 1 pole 2 pole 3 pole 4 pole 1 pole with spring return 2 pole with spring return 3 pole with spring return 1 2 3 4 1 2 3 I I I I I I I I I I1 I I I 1-4 pole 4 pole 1 pole preclose 6° 6 and 7 pole 8 and 9 pole 10 and 11 pole 12 pole 1-4 pole 1 pole mit Rückzug 1-4 pole 1-3 pole 4 pole 1 pole preclose 6° 8 pole 2 pole preclose 6° 5 pole F072 F072 F026 F026 F026 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA4-1 CA10- CA10B- C80CAD4-1 CA25 CA63 C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A710 A711 A712 A713 WAA963 A714 A715 A218 A219 WAA299 WAA294 A210 A211 A212 A213 WAA913 A361 A362 WAA363 WAA364 WAA664 11 Double-throw Switches with Center „OFF“ 60° Switching 1switch type C315 with K handle 2not available for switch type C315 3for use in a three phase four-wire system with switched neutral 1 2 3 4 4 5 6 7 8 8 I I I I I I I I I I I I I I I I I I I I I I I I I I I I K K I I I I I I K K K K Double-throw Switches with Center „OFF“ 90° Switching 1 pole 2 pole 3 pole 4 pole 1 pole preclose 60°3 1 2 3 4 I I I I I I I I I I I I I I I1 I1 Double-throw Switches with Center „OFF“ and electrically isolated contacts 1 pole 2 pole 3 pole 4 pole 4 pole 1 pole preclose 6°3 1 pole with spring return 2 pole to center 1 2 3 4 4 1 2 I I I I I I I I I I I I I I I I I I I I I I I I I I I2 4 pole 1 pole preclose 6° 5 pole 6 and 7 pole 8 pole 1-4 pole 1-4 pole 1 and 2 pole 1-4 pole 8 pole 2 pole preclose 6° 1 pole 2 pole 3 pole 4 pole 4 pole 1 pole preclose 6°3 5 pole 6 pole 7 pole 8 pole 8 pole 2 pole preclose 6°3 4 pole 1 pole preclose 6° F071 F057 F071 F025 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA40 CA4-1 CA10- CA10B- C26CAD4-1 CA25 CA25B C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A214 A215 A216 A320 A321 A322 A310 A312 WAA314 A311 WAA313 WAA315 WAA330 WAA331 WAA332 WAA339 12 Double-throw Switches with Spring Return to Center 1not available for switch type CA25 2not available for switch type C315 3available only up to switch type CA63 1 2 3 1 2 3 General Application Switches 1 pole 2 Gang 2 pole Switching sequence: 3 pole 0, A, A+B 1 pole 3 Gang 2 pole Switching sequence: 3 pole 0, A, A+B, A+B+C 1 pole 2 Gang 2 pole Series switching 3 pole Switching sequence: 0, A, B, A+B 2 pole 2 Gang Series-parallel Switching Switching sequence: 0, A+B series, A, A+B parallel 1 2 3 2 3 5 1 2 3 2 1-3 pole 1-3 pole 1 pole 2 pole 3 pole 1 pole 2 pole 3 pole 1 pole 2 pole 3 pole I I I I I I I I I1 I I I1 I I I I I I I2 I3 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I F025 F261 F075 F001 F001 F001 1 pole with spring return 2 pole to center 3 pole 1 pole with spring return 2 pole from left to center 3 pole < back to table of contents > Dimensions p.56
A540 WAA541 WAA542 A550 WAA551 WAA552 A543 WAA545 Code Type/Handle CA4 CA10 CA40 CA4-1 CA11 CA10B- C26CAD4-1 CA12 CA25B C315 13 Switch Function and Configuration C, CA, CAD Switches Coding Switches/Binary Code Function Escutch. Plate Stages Connection Diagram 0 - 7 360° rotation 0 - 7 complement 360° rotation 0 - 7 + complement 360° rotation 0 - 9 0 - 9 complement 0 - 9 + complement 0 - 11 360° rotation 0 - 11 + complement 360° rotation 2 2 3 2 2 4 2 4 I I I I I I I I I I I I I I I I F322 F322 F322 F007 F007 F007 F009 F009 < back to table of contents > Dimensions p.56
A230 A250 A270 A476 WAA484 WAA489 A231 A251 A271 A477 WAA485 WAA490 A232 A252 WAA272 WAA478 A233 WAA253 WAA273 WAA234 WAA254 WAA274 WAA235 WAA255 WAA275 WAA236 WAA237 WAA238 WAA239 WAA639 Code Type/Handle CA4 CAD.. CA4-1 CA10- CA10B- C80CAD4-1 CA25 CA63 C315 14 Switch Function and Configuration C, CA, CAD Switches Multi-step Switches without „OFF“ 1switch type C315 with K handle 2not available for switch type CA11B Function Escutch. Plate Stages Connection Diagram 1 pole 3 Step 2 pole 3 pole 4 pole 5 pole 6 pole 1 pole 4 Step 2 pole 3 pole 4 pole 5 pole 6 pole 1 pole 5 Step 2 pole 3 pole 4 pole 1 pole 6 Step 2 pole 3 pole 1 pole 7 Step 2 pole 3 pole 1 pole 8 Step 2 pole 3 pole 1 pole 9 Step 1 pole 10 Step 1 pole 11 Step 1 pole 12 Step 1 pole 360° rotation 2 3 5 6 8 9 2 4 6 8 10 12 3 5 8 10 3 6 9 4 7 11 4 8 12 5 5 6 6 6 1 pole 3 pole 4- and 5 pole 6 pole 2 pole 1-3 pole 4-6 pole 1-4 pole 1 and 2 pole 3 pole 1-3 pole 1-3 pole I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I2 I I I K K K I I K K K K I K K K I K K I K K I K K I I I I1 I1 F076 F077 F078 F079 F110 F111 F010 F011 F012 F013 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA4-1 CA10- CA10B- C80CAD4-1 CA25 CA63 C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A240 A260 A280 WAA480 WAA486 WAA491 A241 A261 A281 WAA481 WAA487 15 Multi-step Switches without „OFF“ with electrically isolated contacts A730 A750 A731 A751 1 pole 3 Step 2 pole 1 pole 4 Step 2 pole 2 3 2 4 Multi-step Switches with „OFF“ 1 pole 2 Step 2 pole 3 pole 4 pole 5 pole 6 pole 1 pole 3 Step 2 pole 3 pole 4 pole 5 pole 1 2 3 4 5 6 2 3 5 6 8 2 pole 1-6 pole 1 and 2 pole 3 pole 4 pole 5 pole I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I K I I I K K 1 pole 2 pole 1 pole F076 F077 F075 F109 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA4-1 CA10- CA10B- C80CAD4-1 CA25 CA63 C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A242 WAA262 WAA282 WAA482 A243 WAA263 WAA283 A244 WAA264 WAA284 WAA245 WAA265 WAA246 WAA247 WAA248 WAA249 WAA649 16 Multi-step Switches with „OFF“ 1 pole 4 Step 2 pole 3 pole 4 pole 1 pole 5 Step 2 pole 3 pole 1 pole 6 Step 2 pole 3 pole 1 pole 7 Step 2 pole 1 pole 8 Step 1 pole 9 Step 1 pole 10 Step 1 pole 11 Step 1 pole 360° rotation 2 4 6 8 3 5 8 3 6 9 4 7 4 5 5 6 6 1-4 pole 1-3 pole 1-3 pole 1 pole 2 pole I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I K I I I I I I I I I I I I F002 F003 F004 F005 F006 F007 F008 F009 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CA4-1 CA10- CA10BCAD4-1 CA25 CAD.. CA25B 17 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA002 A004 WAA011 Voltmeter Switches without „OFF“ A023 A025 3 phase 3 wire 3 phase 3 wire 3 phase to phase and phase to neutral 2 3 Voltmeter Switches with „OFF“ 2 pole 360° rotation 3 phase 3 wire 1 2 2 I I I I I I I I I I I S I S S I S S I S F792 F794 F170-PRL F775 F212-PRL < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CA4-1 CA10- CA10BCAD4-1 CA25 CAD.. CA25B Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA005 A007 WAA008 WAA010 Voltmeter Switches with „OFF“ 3 phase to neutral 3 phase to phase and 3 phase to neutral 2 separate 3 phase with center „OFF“ 3 phase and 1 phase to neutral 2 3 4 3 I I I I I I I I I I I I1 I I I F779 F782 F786 18 F789 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA10B- CA4-1 CA10- CA63 C43CAD4-1 CA25 C32 C125 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA046 WAA017 A048 WAA021 WAA036 WAA037 19 1available only up to switch type CA25B Ammeter Switches Single pole with one current transformer Single pole with 3 current transformers without „OFF“ Single pole with 3 current transformers with „OFF“ 360° rotation Single pole with 2 current transformers (3 readings) Single pole with 4 current transformers 2 pole 2 current transformers 1 3 3 2 4 3 I I I I I I I I S I S I S I I S I S1 I S I I F058 F181-PRL F059 F172-PRL F060 F057 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA10BCA4-1 CA10- CA63- C43CAD4-1 CA25 C42 C125 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA019 A038 WAA039 20 Ammeter Switches 1available only up to switch type CA25B 2 pole 3 current transformers 2 pole 4 current transformers 5 5 6 I I I S I I S1 I I I I F181-PRL F059 F060 < back to table of contents > Dimensions p.56
Code Type/Handle C26CA4 CAD.. C43 CA4-1 CA10- CA10B- CA40CAD4-1 CA25 CA25B CA63 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA174 A175 A176 WAA183 A178 WAA177 WAA027 WAA028 WAA033 WAA035 21 Volt-ammeter Switches 1available only up to switch type CA25B 3 phase - phase to phase 3 current 3 phase voltage 3 phase current 4 wire 3 phase voltage 3 phase current 3 wire 6 7 5 5 I I I I I I S S I I S S I1 S1 S1 Control Switches Stop switch Start switch Stop start switch single pole Stop start switch 2 pole Stop start switch with spring return from start to run Stop start switch with spring return to run for 2 units 1 1 1 2 1 2 I I I I I I I I I I I I I I I I I I I1 I1 I1 I I I1 Type/Griff F101 F077 F174-PRL F174-PRL F022 F023 F024 F024 F119 F121 < back to table of contents > Dimensions p.56
Code Type/Handle C26CA4 CAD.. C43 CA4-1 CA10- CA10B- CA40CAD4-1 CA25 CA25B CA63 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA190 WAA192 A789 A791 WAA790 WAA179 WAA537 WAA182 WAA150 22 Control Switches 1Advise the indicator device, described in Catalog 101, page 9. 2not available for switch types CA25 and CA25B 3incl. slip clutch 4available only up to switch type CA40 Stop start switch with spring return to run with contactor interlock contactors for 2 units Motor voltage control switch 2 2 Control Switches with electrically isolated contacts Stop start switch single pole Stop start switch with spring return to 1 Stop start switch with spring return to run for 2 units Contactor control with spring return to „OFF“ Circuit breaker control 1 1 2 2 2 Control and Alarm Switches1 With slip clutch and without indicator device Without indicator device 53 2 I I I P I P I I I I I I I I I I P I I I I P I4 I4 I4 I B2 B2 B2 F121 F144-PRL F024 F119 F121 F025 F143-PRL < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA..B CA4-1 CA10- C26-C43 C80CAD4-1 CA25 CA40-CA63 C315 23 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram WAA451 WAA457 Motor Reversing Switches 1not available for switch type CA25 2not available for switch types C26-C43, CA40-CA63 3available only up to switch type CA50 Motor Control Switches 2 speed 2 winding 0-A-B s or d 3 speed 2 winding 0-A-B s or d 3 6 A400 A401 A228 WAA402 2 pole 3 pole 3 pole with spring return to „OFF“ 3 pole for use with reversing contactors 2 3 3 4 I I I I I I I1 I I I I2 I3 I I I I I I I I I K F071 F071 F025 F121 F073 F109 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA40 CA4-1 CA10- CA10B- C26CAD4-1 CA25 CA25B C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A440 A466 A441 A442 WAA444 WAA468 24 Motor Control Switches 1incl. slip clutch 2 speed single winding 2 speed single winding without „OFF“ 2 speed single winding with center „OFF“ 2 speed single winding reversing 2 speed single winding for use with contactors 2 speed reversing for 2 way operation with slip clutch for „OFF“ load use 4 4 4 6 5 101 I I I I I I I I I I I I I I I I I I I I I I I F073 F072 F071 F105 F073 F294 < back to table of contents > Dimensions p.56
Code Type/Handle CA4 CAD.. CA..B CA4-1 CA10- C26-C43 C80CAD4-1 CA25 CA40-CA63 C315 Switch Function and Configuration C, CA, CAD Switches Function Escutch. Plate Stages Connection Diagram A425 WAA426 WAA622 A410 WAA413 WAA416 A419 25 Star-delta Switches 1not available for switch type CA25 OFF-star-delta Reversing With auxiliary contact closed in „OFF“ position For use with reversing contactors 4 5 5 4 Start and Run Switches Split-phase start Split-phase start reversing Split-phase reversing auto cutout of start field winding 2 3 3 Split-phase Start FLD Split-phase Start FLD Split-phase Start FLD I I I I I I I I I I I I I I I K I I I I1 I I I I I F080 F112 F080 F061 F119 F120 F104 < back to table of contents > Dimensions p.56
Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 26 Switch Function and Configuration L Switches Additional length for switches size S2 for mounting E/EF = 27 mm Additional length for switches size S3 for mounting E/EF = 31,5 mm and mounting ER/VE = 20,1 mm ON/OFF Switches with 60° Switching 1 pole L350 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 1 2 3 4 1-4 pole 1 pole L351 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 1 2 3 4 1-4 pole 1 pole L400 2 pole 3 pole 4 pole 3 pole with lugs suitable for protective cover F070 F070 K K K K K WAA200 WAA201 WAA202 WAA203 WAA302 2 2 4 4 3 1-4 pole WAA302 1 pole L600 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 3 3 6 6 1-4 pole 1 pole L630 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 2 4 6 8 1-4 pole 1 pole L631 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 2 4 6 8 1-4 pole 1 pole L800 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 2 4 6 8 1-4 pole 1 pole L1000 2 pole 3 pole 4 pole F070 K K K K WAA200 WAA201 WAA202 WAA203 3 6 9 12 1-4 pole 1 pole L1200 2 pole 3 pole F070 K K K WAA200 WAA201 WAA202 3 6 9 1-3 pole 1 pole L1600 2 pole 3 pole F070 K K H WAA200 WAA201 WAA202 4 8 12 1-3 pole 1 pole L2000 2 pole F070 K H WAA200 WAA201 5 10 1 and 2 pole < back to table of contents > Dimensions p.56
27 Switch Function and Configuration L Switches Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 Additional length for switches size S2 for mounting E/EF = 27 mm Additional length for switches size S3 for mounting E/EF = 31,5 mm and mounting ER/VE = 20,1 mm ON/OFF Switches with 90° Switching 1 pole L350 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K K WAA290 WAA291 WAA292 WAA293 1 2 3 4 1-4 pole 1 pole L351 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K K WAA290 WAA291 WAA292 WAA293 1 2 3 4 1-4 pole 1 pole L400 2 pole 3 pole 4 pole 1 pole preclose 60° 3 pole with lugs suitable for protective cover 3 pole 360° rotation F056 F056 F062 K K K K K K WAA290 WAA291 WAA292 WAA293 WAA307 WAA208 2 2 4 4 3 4 1-4 pole WAA307 1 pole L600 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K H WAA290 WAA291 WAA292 WAA293 3 3 6 6 1-3 pole 4 pole 1 pole L630 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K K WAA290 WAA291 WAA292 WAA293 2 4 6 8 1-3 pole 4 pole 1 pole L631 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K K WAA290 WAA291 WAA292 WAA293 2 4 6 8 1-3 pole 4 pole 1 pole L800 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K H WAA290 WAA291 WAA292 WAA293 2 4 6 8 1-3 pole 4 pole 1 pole L1000 2 pole 3 pole 4 pole 1 pole preclose 60° F056 K K K K WAA290 WAA291 WAA292 WAA293 3 6 9 12 1-3 pole 4 pole 1 pole L1200 2 pole 3 pole F056 K K H WAA290 WAA291 WAA292 3 6 9 1-3 pole 1 pole L1600 2 pole 3 pole F056 K H H WAA290 WAA291 WAA292 4 8 12 1-3 pole 1 pole L2000 2 pole F056 K H WAA290 WAA291 5 10 1- und 2 pole < back to table of contents > Dimensions p.56
Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 28 Switch Function and Configuration L Switches Additional length for switches size S2 for mounting E/EF = 27 mm Additional length for switches size S3 for mounting E/EF = 31,5 mm and mounting ER/VE = 20,1 mm Double-throw Switches without „OFF“ 60° Switching 1 pole L350 2 pole 3 pole 4 pole F072 K K K K WAA220 WAA221 WAA222 WAA223 2 4 6 8 1-4 pole 1 pole L351 2 pole 3 pole 4 pole F072 K K K K WAA220 WAA221 WAA222 WAA223 2 4 6 8 1-4 pole 1 pole L400 2 pole 3 pole 4 pole F072 K K K K WAA220 WAA221 WAA222 WAA223 2 4 6 8 1-4 pole 1 pole L600 2 pole 3 pole 4 pole F072 K K K H WAA220 WAA221 WAA222 WAA223 3 6 9 12 1-4 pole 1 pole L630 2 pole 3 pole F072 K K K WAA220 WAA221 WAA222 4 8 12 1-3 pole 1 pole L631 2 pole 3 pole F072 K K K WAA220 WAA221 WAA222 4 8 12 1-3 pole 1 pole L800 2 pole 3 pole F072 K K K WAA220 WAA221 WAA222 4 8 12 1-3 pole 1 pole L1000 2 pole F072 K K WAA220 WAA221 6 12 1 and 2 pole 1 pole L1200 F072 K WAA220 6 1 pole L1600 F072 K WAA220 8 1 pole L2000 F072 H WAA220 10 < back to table of contents > Dimensions p.56
29 Switch Function and Configuration L Switches Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 Additional length for switches size S2 for mounting E/EF = 27 mm Additional length for switches size S3 for mounting E/EF = 31,5 mm and mounting ER/VE = 20,1 mm Double-throw Switches with Center „OFF" 60° Switching 1 pole L350 2 pole 3 pole 4 pole F071 K K K K WAA210 WAA211 WAA212 WAA213 2 4 6 8 1-4 pole 1 pole L351 2 pole 3 pole 4 pole F071 K K K K WAA210 WAA211 WAA212 WAA213 2 4 6 8 1-4 pole 1 pole L400 2 pole 3 pole 4 pole F071 K K K K WAA210 WAA211 WAA212 WAA213 2 4 6 8 1-4 pole 1 pole L600 2 pole 3 pole 4 pole F071 K K K H WAA210 WAA211 WAA212 WAA213 3 6 9 12 1-4 pole 1 pole L630 2 pole 3 pole F071 K K K WAA210 WAA211 WAA212 4 8 12 1-3 pole 1 pole L631 2 pole 3 pole F071 K K K WAA210 WAA211 WAA212 4 8 12 1-3 pole 1 pole L800 2 pole 3 pole F071 K K K WAA210 WAA211 WAA212 4 8 12 1-3 pole 1 pole L1000 2 pole F071 K K WAA210 WAA211 6 12 1 and 2 pole 1 pole L1200 F071 K WAA210 6 1 pole L1600 F071 K WAA210 8 1 pole L2000 F071 H WAA210 10 < back to table of contents > Dimensions p.56
Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 30 Switch Function and Configuration L Switches 3 Step L350 F076 K WAA230 4 3 Step L351 F076 K WAA230 4 3 Step L400 F076 K WAA230 4 4 Step L350 F077 K WAA231 4 4 Step L351 F077 K WAA231 4 4 Step L400 F077 K WAA231 4 5 Step L350 F078 K WAA232 6 5 Step L351 F078 K WAA232 6 5 Step L400 F078 K WAA232 6 6 Step L350 F079 K WAA233 6 6 Step L351 F079 K WAA233 6 Multi-step Switches single pole without „OFF“ < back to table of contents > Dimensions p.56
31 Switch Function and Configuration L Switches Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 Dimensions p.56 6 Step L400 F079 K WAA233 6 7 Step L350 F110 K WAA234 8 7 Step L351 F110 K WAA234 8 7 Step L400 F110 K WAA234 8 8 Step L350 F111 K WAA235 8 8 Step L351 F111 K WAA235 8 8 Step L400 F111 K WAA235 8 9 Step L350 F010 K WAA236 10 9 Step L351 F010 K WAA236 10 9 Step L400 F010 K WAA236 10 10 Step L350 F011 K WAA237 10 Multi-step Switches single pole without „OFF“ < back to table of contents >
Function/Type Escutch. Plate Handle Code Stages Double Latching Connection Diagram L350 L630 L1000 L351 L631 32 Switch Function and Configuration L Switches 10 Step L351 F011 K WAA237 10 10 Step L400 F011 K WAA237 10 11 Step L350 F012 K WAA238 12 11 Step L351 F012 K WAA238 12 11 Step L400 F012 K WAA238 12 12 Step L350 F013 K WAA239 12 12 Step L351 F013 K WAA239 12 12 Step L400 F013 K WAA239 12 Multi-step Switches single pole without „OFF“ < back to table of contents > Dimensions p.56
33 Mounting CA4, CA4-1, CAD4-1 Code CA4 CA4-1 CAD4-1 E E-V EF EF-V E9 E91 E92 E93 E94 Panel Mount Two hole, Protection IP 40 Two hole Protection IP 66/67/69k Two hole with shaft for radio knobs, Protection IP 40 Shaft diam. 6 mm/.24 inch Shaft diam. 6.35 mm/.25 inch, Protection IP 40 Mosaic Mount For Siemens-Mosaic 30 mm grid depth, Protection IP 40 For Subklew-, Kreutzenbeck-, Symo-Mosaic, Protection IP 40 28 mm 25 mm 25 mm grid depth For Mauell-Mosaic 30 mm grid depth, Protection IP 40 Terminals rotated 90° Two Hole Panel Mount or Mosaic Mount < back to table of contents >
34 Mounting C, CA, CAD, L Switches Code Terminals rotated 90° E E-V EF EF-V E22 E22-V EG EGF ER ERF CAD.. CA10CA25 CAD.. CA10CA25 CA40- CA63 CA40- CA63 C80- C200-4 C80- C200-4 Panel Mount Four hole, Protection IP 40 Four hole, Protection IP 66/67/69k Two hole, Protection IP 66/69k Panel mount using larger face plate, handle and heavy duty stop Four hole, Protection IP 40 Four hole, Protection IP 66/67/69k Double End Mount Four hole, Protection IP 40 Four hole, Protection IP 66/67/69k Two or Four Hole Panel Mount C315 L400L2000 Size S3 CAD.. CA10CA25 CA10BCA63 C42 C43 C80C200-4 L350 Size S2 < back to table of contents >
35 Mounting C, CA, CAD Switches Panel mount with heavy duty latching and metal shaft Four hole, Protection IP 40 48 x 48 Plate – S0 Four hole, Protection IP 40 64 x 64 Plate – S1 Four hole, Protection IP 40 64 x 64 Plate – S1 complete with 6mm square metal shaft Panel mount with protective cover Four hole Protection front IP 40 rear IP 30 Four hole with additional shaft seal Protection front IP 65 rear IP 30 Four hole Protection front IP 40 rear IP 42 Four hole with additional shaft seal Protection front IP 65 rear IP 42 Two hole Protection front IP 66/69k rear IP 42 Two or Four Hole Panel Mount Code C32 C42 CA40 CA50 CA63 C43 CA10B CA11B CA20B CA25B CAD.. CA10CA25 KN2 KN1 KD1 EC ED EC1 ED1 ED22 CAD.. CA10CA25 CAD.. CA10CA25 CAD.. CA10CA25 < back to table of contents >
Single Hole Mount 36 Mounting C, CA, CAD Switches Code Terminals rotated 90° CAD.. CA10CA25 CA4 CA4-1 CAD4-1 FS1 FS1-V FT1 FT1-V FT3 FT3-V FS2 FS2-V FT2 FT2-V FT4 FT4-V FH3 FH3-V FS4 FS4-V FT6 FT6-V FH4 FH4-V S00 T170 09 mm 16/22 16/22 16/22 16/22 16/22 16/22 mm 22 22 22/30 22/30 22 22 22/30 22/30 22 22 22 22 22 22 Single Hole Mount complete with lock nut and shaft seal Bezel mount, Protection IP 66/67/69k Square face plate, Protection IP 66/67/69k S1 square face plate and heavy duty stop, Protection IP 66/67/69k Rectangular face plate, Protection IP 66/67/69k S1 rectangular face plate and heavy duty stop, Protection IP 66/67/69k Lock nut spanner < back to table of contents >
37 Mounting C, CA, CAD, L Switches Base Mount Code Terminals rotated 90° CA10BCA63 C42 CAD.. CA10CA25 C43 C80L2000 VE VE-V VF VF-V VE22 VE22V VF22 VF22V VE1 Base Mount Four hole, Protection IP 40 Four hole with integrated simplified door clutch, Protection IP 65 Two hole, Protection IP 40 Two hole with integrated simplified door clutch, Protection IP 65 Snap-on for DIN Rail EN 60715, Protection IP 40 CAD.. CA10CA25 CAD.. CA10CA25 CAD.. CA10CA25 CAD.. CA10CA25 < back to table of contents >
Base Mount 38 Mounting C, CA, CAD, L Switches Code VE2 VE21 VE21V DIN Rail Mount Snap-on for DIN Rail EN 60715 with face plate for 45 mm standard knock-out. Snap-on for DIN Rail EN 60715. With face plate for 45 mm standard knock-out. The handle and plate are adjustable in height. CAD.. CA10CA25 CA4 CA4-1 CAD4-1 CAD.. CA10CA20 CA25 < back to table of contents >
39 Mounting C, CA, CAD Switches Mounting Plates for Plaster Depth Boxes acc. to DIN 49073 and ÖNORM E8608 Code CAD.. CA10CA25 UE1 UE2 UE3 Plaster depth trim, Protection IP 40 With light, Protection IP 40 With facility for light addition, Protection IP 40 < back to table of contents >
40 Face plates Square and rectangular face plates are available for each size of switch. The face plate consists of a frame and a faceplate having the switch positions which is than embossed with hot-foil backing. The face plate frame is an essential part of the switch and serves as a bearing surface for the handle. If the switch is to be mounted without an face plate we would recommend for size S1, S2 and S3 the handle bearing plate T100-04. Standard Letterings Available (Over 500 standard letterings, special letterings upon request.) 30° switching 45° switching F022 F141 F158 F703 F023 F137 F142 F159 F701 F704 F152 F709 F026 F035 F153 F169 F024 F143 F160 F221 F222 F224 F025 F034 F036 F037 F038 F039 F139 F144 F147 F149 F150 F151 F219 F258 F259 F273 F280 F329 F384 F708 F053 F161 F297 F298 F306 F307 F001 F040 F052 F229 F355 F018 F019 F029 F030 F154 F155 F165 F166 F183 F184 F301 F302 F321 F332 F333 F334 F335 F374 F711 F712 F002 F021 F033 F041 F055 F305 F319 F054 F003 F042 F138 F255 F299 F308 F353 F350 F351 F004 F014 F017 F020 F027 F028 F031 F032 F043 F049 F135 F156 F157 F162 F167 F168 F187 F189 F303 F304 F336 F337 F347 F348 F710 F713 F714 F734 F005 F044 F136 F140 F702 F006 F010 F045 F015 F050 F007 F011 F046 F008 F012 F047 F016 F051 F009 F013 F048 F748 F782 F783 F784 F785 F786 F787 F788 F799 F111 F210 F211 F284 F285 F296 F322 F727 F740 F739 F741 F419 F789 F790 F791 F794 F795 F110 F106 F116 F294 F317 F414 F415 F416 F417 F418 F775 F776 F777 F778 F779 F780 F781 F796 F797 F798 F105 F108 F112 F113 F117 F118 F293 F429 F217 F267 F289 F330 F375 F376 F383 F408 F409 F410 F411 F412 F413 F426 F427 F430 F729 F752 F747 F295 F742 F743 F215 F216 F738 F744 F746 F792 F793 F107 F109 F114 F115 F212 F213 F214 < back to table of contents >
41 Face plates 1INTERRUPTEUR PRINCIPAL, OUVERTURE EN POSITION 0 2INTERRUTTORE GENERALE, APRIRE SOLO CON MANIGLIA SU 0 3INTERRUPTOR PRINCIPAL, ABRIR ARMARIO SOLO EN POS. ’’0’’ 60° switching 90° switching Miscellaneous F056 F063 F068 F134 F201 F251 F252 F346 F456 F058 F065 F069 F177 F178 F182 F208 F253 F254 F340 F360 F378 F458 F443 F700 F743 F057 F061 F064 F067 F171 F181 F205 F207 F209 F320 F349 F445 F437 F715 F719 F059 F060 F062 F066 F170 F172 F173 F174 F175 F176 F179 F180 F186 F188 F202 F204 F206 F250 F265 F266 F286 F318 F327 F338 F339 F425 F716 F717 F718 F726 F733 F751 F755 F756 F070 F087 F088 F089 F133 F197 F198 F232 F243 F247 F263 F268 F310 F311 F323 F328 F352 F367 F379 F380 F470 F754 F072 F163 F164 F192 F193 F196 F230 F231 F234 F244 F257 F262 F264 F282 F288 F291 F313 F382 F441 F705 F721 F722 F750 F757 F758 F075 F076 F098 F220 F223 F356 F357 F377 F723 F071 F073 F080 F081 F085 F086 F090 F091 F092 F093 F094 F104 F194 F235 F371 F237 F239 F240 F241 F249 F260 F269 F274 F281 F290 F292 F312 F314 F315 F316 F324 F331 F344 F354 F358 F359 F364 F370 F373 F381 F385 F442 F469 F444 F732 F735 F759 F077 F100 F101 F102 F309 F342 F343 F361 F362 F363 F365 F366 F078 F191 F325 F326 F720 F074 F082 F096 F097 F195 F724 F256 F079 F083 F084 F095 F099 F185 F190 F199 F233 F236 F238 F242 F283 F725 F730 F731 F736 F737 F823 F824 F825 F826 F827 F828 F829 F830 F831 F832 F833 F834 F835 F837 F805 F806 F807 F808 F809 F810 F811 F812 F813 F814 F815 F816 F817 F818 F119 F130 F122 F126 F125 F129 F225 F248 F261 F341 F345 F287 F123 F127 F145 F146 F148 F706 F707 F245 F120 F124 F128 F131 F121 F132 F749 F990 F991 F838 F839 F840 F841 INTERRUPTEUR PRINCIPAL OUVERTURE EN POSITION 0 INTERRUTTORE GENERALE APRIRE SOLO CON MANIGLIA SU 0 INTERRUPTOR PRINCIPAL ABRIR ARMARIO SOLO EN POS. ’’0’’ 1 2 3 F801 F802 F803 F804 F819 F820 F821 F822 < back to table of contents >
42 Handles Type Color Code Size S00 S0 S1 S2 S3 Type Color Code Size S00 S0 S1 S2 S3 R-Handle F-Handle S-Handle P-Handle Handwheel black red G001 G002 — — black red G221 G222 — — black red G301 G302 — — — — — — black red G211 G212 — — black G971 — — — — black red G251 G252 black red G521 G522 — — — — — — black red G501 G502 — — — — — — — — black red G411 G412 — — — — black red G321 G322 — — — — — — — — I-Handle B-Handle L-Handle K-Handle O-Handle S0 S1 S0 S1-S3 S00 S0-S3 < back to table of contents >
International Standards and Approvals 43 IEC 609474 Country Authority Mark or Standard USA Underwriters Laboratories Inc. Canada UL investigated acc. to CSA International Electrical Commission (IEC) Recommendation China China Quality Certification Centre Russia Eurasian Conformity Belarus Kazakhstan Russian Russian Maritime Federation Register of Shipping Lloyds Register EMEA 5 1 2 2 1 3 3 Switch approved + Switch conforms to requirements 1Approved under the “Component Program” (UL-Recognized Industrial Component). File No. E35541, Category Control No. NLRV2 (U.S.) and NLRV8 (Canada) resp. File No. E60262, Category Control Number NRNT2 (U.S.) and NRNT8 (Canada). 2Approved under the “Listing Program”. File No. E35541, Category Control No. NLRV (U.S.) resp. NLRV7 (Canada). 3Switch types CAD11/CAD12 approved under the “Listing Program”. File No. E60262, Category Control No. NRNT (U.S.) resp. NRNT7 (Canada). 4IEC does not operate an approval scheme. 5File No. 13002ass No. 3211-05 resp. 4652-04. CAD11/12 CA10 CA10B C26 CA40 C43 L350/1 L400 L1200 CA4 CA11 CA11B CA25 C32 CA50 C80 C315 L630/1 L600 L1600 CA4-1 CA20 CA20B CA25B C42 CA63 C125 C316 L1000 L800 L2000 + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + < back to table of contents >
Technical Data C, CA Switches Selection Data CA4 CA10 CA11 CA20 CA25 C42 C315 CA4-1 CA10B CA11B CA20B CA25B C26 C32 C43 CA40 CA50 CA63 C80 C125 C200-4 C316 44 1Valid for lines with grounded common neutral termination, overvoltage category III, pollution degree 3. Values for other supply systems on request. 2Valid for CA4 only. 3International Standards and Approvals, refer to page 43. 4For electromagnetic optional extras see additional data in Catalog 101. 5Storage temperature: -40 °C to 85 °C (in case of temperature below -5 °C no shock load permissible). Rated Insulation Voltage Ui IEC 60947-3, EN 60947-3 1 VDE 0660 part 1071 SEV4 UL/Canada CEE/NEMKO min. voltage Rated Impulse Withstand Voltage Uimp Rated Thermal Current Iu/Ith IEC 60947-3, EN 60947-3 VDE 0660 part 107 SEV3 380 V 660 V UL/Canada Rated Operational Current Ie AC-21A Switching of resistive IEC 60947-3, EN 60947-3 loads, including mo- VDE 0660 690 V derate overloads part 107 AC-1 Resistive or low SEV4 380 V inductive loads 660 V AC-22A Switching of combined re- IEC 60947-3, EN 60947-3 sistive or low inductive loads VDE 0660 220 V-500 V including moderate overloads part 107 660 V-690 V AC-15 Switching of control IEC 60947-5-1, EN 60947-5-1 devices, contactors, VDE 0660 220 V-240 V valves etc. part 200 380 V-440 V Pilot Duty UL/Canada3 Heavy Ampere Rating UL/Canada3 Resistive or low inductive loads Resistive load/motor load CEE NEMKO Breaking capacity 220 V-240 V 380 V-440 V 660 V-690 V Power loss per contact at Iu Resistance to vibration Resistance to shock Short Circuit Protection Max. fuse size (gG-characteristic) Rated short-time withstand current (1s-current) Min. Ambient Temperature of Stages Max. Ambient Temperature of Stages5, 7 open at 100 % I u/Ith enclosed at 100 % Ithe V V V V kV A A A A A A A A A A A VAC A A A A A A W A A 440 690 690 690 690 690 690 690 690 690 690 690 690 690 690/1000 380 660 660 660 690 660 660 660 690 690 690 660 660 – 660 300 300 600 600 300 600 600 600 600 600 600 600 600 – 600 400/380 380 400 400 – 400 400 400 – – – 400 – – – on request 4 6 6 6 6 6 6 6 6 6 6 6 6 6 6/8 10 20 20 25 32 32 50 63 40 50 63 115 150 200 315 10 16 16 25 32 32 40 63 40 50 63 100 150 – 315 – 12 12 25 32 32 40 63 40 50 63 – – – 315 10 20 20 30 30 40 50 65 45 55 65 100 150 – 240 10 20 20 25 32 32 40 63 40 50 63 100 150 200 315 10 16 16 25 32 32 40 63 40 50 63 100 150 – 315 – 12 12 20 32 32 40 63 40 50 63 – – – 315 10 20 20 25 32 32 40 63 40 50 63 100 150 150 315 – 20 20 25 32 32 40 63 40 50 63 100 125 125 125 2,5 6 6 8 12 14 16 – 14 16 16 – – – – 1,5 4 4 5 6 6 7 – 6 7 7 – – – – A300 A300 A600 A600 A300 A600 A600 A600 A600 A600 A600 – – – A600 10 20 20 30 30 40 50 65 45 55 60 100 150 – 240 4/2 10/6 10/6 16/10 – 25/1032/10 40/10 – – – 63/10 – – – 6/42 10/6 – 20/10 – – – – – – – – – – – 50 150 150 200 280 280 380 550 290 330 440 860 1100 1100 2000 50 150 150 200 250 250 360 550 290 330 440 860 1100 1100 2000 – 80 80 125 150 150 270 365 170 200 260 400 490 490 340 0,4/0,9 0,9 0,9 0,9 0,7 1.3 1.3 1.7 1 1,8 2,8 5,8 3,8 6,7 17 min. 4 g, 2-100 Hz, 1,6 mm on request min. 5 g, 6 ms min. 5 g, 30 ms 10 25 25 35 35 50 63 80 50 63 63 125 200 200 315 60 140 140 280 480 350 800 1000 950 950 950 1300 2000 2000 4200 -25 °C (valid only without optional extra, C315/C316 on request) 55 °C during 24 hours with peaks up to 60 °C 35 °C during 24 hours with peaks up to 40 °C < back to table of contents >
45 Technical Data C, CA Switches Selection Data CA4 CA10 CA11 CA20 CA25 C42 C315 CA4-1 CA10B CA11B CA20B CA25B C26 C32 C43 CA40 CA50 CA63 C80 C125 C200-4 C316 Rated Utilization Category IEC 60947-3, EN 60947-3 VDE 0660 part 107 AC-2 Slip ring motor starting, 3 phase 220 V-240 V reversing and plugging, 3 pole 380 V-440 V star-delta starting 500 V CA4-CA50 660 V-690 V AC-3 Direct-on-line starting, 3 phase 220 V-240 V star-delta starting 3 pole 380 V-440 V CA63-C315 500 V 660 V-690 V 1 phase 110 V-120 V 2 pole 220 V-240 V 380 V-440 V AC-4 Direct-on-line starting, 3 phase 220 V-240 V reversing, plugging and 3 pole 380 V-440 V inching 500 V 660 V-690 V 1 phase 110 V-120 V 2 pole 220 V-240 V 380 V-440 V AC-23A Frequent switching of 3 phase 220 V-240 V motors or other high 3 pole 380 V-440 V inductive loads 500 V 660 V-690 V 1 phase 110 V-120 V 2 pole 220 V-240 V 380 V-440 V Ratings UL/Canada Standard motor load 3 phase 110 V-120 V DOL-Rating 3 pole 220 V-240 V (similar AC-3) 440 V-480 V 550 V-600 V 1 phase 110 V-120 V 2 pole 220 V-240 V 277 V 440 V-480 V 550 V-600 V Heavy motor load 3 phase 110 V-120 V Reversing-Rating 3 pole 220 V-240 V (similar AC-4) 440 V-600 V 1 phase 110 V-120 V 2 pole 220 V-240 V 277 V kW kW kW kW kW kW kW HP HP HP HP 2,5 4 4 5,5 7,5 8 10 18,5 10 11 18,5 30 37 37 55 4,5 7,5 7,5 11 15 15 18,5 30 18,5 22 30 45 55 55 90 – 10 10 15 18,5 18,5 22 40 22 30 40 55 75 75 110 – 10 10 13 15 15 22 37 22 30 37 55 55 55 55 1,5 3 3 4 5,5 5,5 7,5 11 7,5 11 11 15 22 22 37 2,2 5,5 5,5 7,5 11 11 15 18,5 15 18,5 18,5 30 37 37 55 – 5,5 5,5 7,5 11 11 15 18,5 15 18,5 18,5 30 37 37 55 – 5,5 5,5 7,5 11 11 15 18,5 15 18,5 22 30 30 30 37 0,3 0,6 0,6 1,5 2,2 2,2 2,5 3 2,5 3 3 3,7 5,5 5,5 11 0,55 2,2 2,2 3 4 4 5,5 6 5,5 6 6 7,5 11 11 22 0,75 3 3 3,7 5,5 5,5 7,5 11 7,5 11 11 13 18,5 18,5 30 0,37 0,55 0,55 1,5 2,5 2,7 3,7 5,5 3,7 4 5,5 6 10 10 15 0,55 1,5 1,5 3 5,5 5,5 6 7,5 6 7 7,5 11 15 15 25 – 1,5 1,5 3 5,5 5,5 6 7,5 6 7 7,5 11 15 15 25 – 1,5 1,5 3 5,5 5,5 6 7,5 6 7,5 9 11 15 15 22 0,15 0,3 0,3 0,45 0,75 0,75 1,1 1,2 1,1 1,2 1,2 1,5 2,2 2,2 4 0,25 0,75 0,75 1,1 1,5 1,5 2,2 2,4 2,2 2,4 2,4 3 4 4 7,5 0,5 1,5 1,5 2,2 3 3 3,7 4 3,7 4 4 5,5 7,5 7,5 11 1,8 3,7 3,7 5,5 7,5 7,5 11 15 7,5 11 15 30 37 37 75 3 7,5 7,5 11 15 15 22 30 18,5 22 30 45 75 75 132 – 7,5 7,5 11 15 15 30 45 18,5 22 30 55 90 90 132 – 7,5 7,5 11 15 15 22 40 18,5 22 30 45 55 55 37 0,37 0,75 0,75 1,5 2,2 2,2 2,5 4 2,2 2,5 4 5,5 11 11 18,5 0,75 2,5 2,5 3 4 4 5,5 10 4 5,5 10 15 22 22 37 1,1 3,7 3,7 5,5 7,5 7,5 11 18,5 7,5 11 18,5 22 37 37 55 0,75 1,5 1,5 3 5 5 7,5 7,5 7,5 7,5 7,5 10 15 – 30 1 3 3 7,5 10 10 15 15 15 15 15 20 25 – 75 – – 5 10 – 20 25 25 25 25 30 30 40 – 75 – – 5 10 – 25 30 30 25 30 30 40 50 – 60 0,33 0,5 0,5 1,5 2 2 3 3 3 3 3 5 7,5 – 15 0,75 1 1 3 5 5 7,5 7,5 7,5 7,5 7,5 10 15 – 40 0,75 2 2 3 5 5 7,5 7,5 7,5 7,5 10 10 15 – 40 – – 2 5 – 10 15 15 15 15 15 20 25 – 50 – – 2 5 – 15 20 20 15 20 20 25 30 – 50 – 0,5 0,5 1 2 2 3 5 – – – 7,5 10 – 15 – 1 1 2 3 3 5 7,5 – – – 15 20 – 30 – – 3 5 – 10 15 20 – – – 25 30 – 40 – 0,17 0,17 0,33 1,5 1,5 1,5 2 – – – 3 5 – 7,5 – 0,5 0,5 0,75 3 3 3 5 – – – 7,5 10 – 15 – 0,6 0,6 1 3 3 3 5 – – – 7,5 10 – 15 < back to table of contents >
46 Max. Permissible Wire Gage - Use copper wire only Single-core or stranded wire Flexible wire (sleeving in accordance with DIN 46228) Flexible AWG wires (without sleeve) Tightening torque of screws mm2 AWG mm2 AWG Nm Ib-in 2x 2x 2x 2x 2x 2x 2x 2x 1,5 2,5 2,5 4 6 6 10 16 16 16 16 35 70 951 1851 14 12 12 10 8 8 8 6 6 6 6 2 2/0 – MCM 350 2x 2x 2x 2x 2x 2x 2x 2x 1,5 2,5 2,5 4 4 6 6 10 10 10 10 25 50 951 1501 (1) (2,5) (2,5) (2,5) (4) (4) (6) (10) (10) (10) (10) (25) (50) 16 14 14 12 10 10 8 6 6 6 6 3 1/0 – MCM 300 0,4 0,6 0,6 1,3 1,3 1,3 2,2 3 1,8 1,8 1,8 4 4,5 8 14 3,5 5 5 12 12 12 19,5 26,4 16 16 16 35 39,8 70 125 1Cable lug must accept M8 (C200-4) and M12 (C315/C316) screw. 2Values for switches with spring return on request. A A A A A A A A A A A A A A A A A A A A DC Switching Capacity2 contacts in series: 1 2 3 4 5 6 8 Permissible voltage in volts Utilization category 24 48 72 96 120 144 192 DC-21A 48 96 144 192 240 288 384 Switching of resistive load 60 120 180 240 300 360 480 Time constant L/R≤1ms 110 220 330 440 550 660 – 220 440 660 – – – – Utilization category 24 48 72 96 120 144 192 DC-22A 48 96 144 192 240 288 384 Switching of mixed resistive 60 120 180 240 300 360 480 and inductive load 110 220 330 440 550 660 – f.e. shunt motors 220 440 660 – – – – Time constant L/R≤2,5ms Utilization category 24 48 72 96 120 144 192 DC-23A 48 96 144 192 240 288 384 Switching of highly 60 120 180 240 300 360 480 inductive loads 110 220 330 440 550 660 – f.e. series motors 220 440 660 – – – – Time constant L/R≤15ms Utilization category 24 48 – – – – – DC-13 48 96 – – – – – Control of electromagnets 60 120 – – – – – Time constant L/R≤100ms 110 220 – – – – – 220 440 – – – – – Rated Operational Current Ie CA4 CA10 CA10S CA20 CA20S CA25 CA25S CA40 CA40S CA63S 10 16 16 21 24 26 32 35 40 63 6 14 15 18 24 25 32 32 40 63 5 13 15 17 21 24 28 28 40 50 4 6 7 6 7 7 9,3 – – – 0,8 0,9 1 1 1 1 1 – – – 8 14 15 18 24 25 32 35 40 63 5 13 15 17 24 25 32 32 40 63 4 12 15 16 19 24 25 – 20 25 1,5 1,9 2 2 2 2,25 3 – – – 0,3 0,3 0,35 0,3 0,35 0,35 0,35 – – – 7 13 15 16 23 23 32 35 40 63 4 12 15 15 23 21 32 26 40 63 3,5 10 13 14 16 18 25 – – – 1 1,5 1,75 1,7 1,75 2 2,5 – – – 0,2 0,2 0,3 0,2 0,3 0,2 0,3 – – – 0,8 3 – 4 – 5 – – – – 0,5 1,7 – 2,4 – 3 – – – – 0,2 1,4 – 1,8 – 2,5 – – – – – 0,7 – 1 – 1,5 – – – – – 0,15 – 0,35 – 0,5 – – – – Technical Data C, CA Switches Selection Data CA4 CA10 CA11 CA20 CA25 C42 C315 CA4-1 CA10B CA11B CA20B CA25B C26 C32 C43 CA40 CA50 CA63 C80 C125 C200-4 C316 Ring cable lug – Dimensions B A C H A (mm) B (mm) C (mm) H (mm) C26-6 10 M4 5 3,7 C32-6 12,9 M5 6,1 3,8 C42-6 15,6 M6 7,1 4,1 C80-6 23,1 M6 9,1 5,4 C125-6 28,5 M6 11,8 4,9 C200-4 – M8 – 4,8 C315 23,6 M12 18,3 3,4 < back to table of contents >
Technical Data L Switches Selection Data L350 L630 L351 L400 L600 L631 L800 L1000 L1200 L1600 L2000 1Valid for lines with grounded common neutral termination, overvoltage category III, pollution degree 3. Values for other supply systems on request. 2International Standards and Approvals, refer to page 43. 3For electromagnetic optional extras see additional data in Catalog 101. 4Storage temperature: -40 °C to 85 °C (in case of temperature below -5 °C no shock load permissible). Rated Insulation Voltage Ui IEC 60947-3, EN 60947-3 1 VDE 0660 part 1071 UL/Canada2 min. voltage Rated Impulse Withstand Voltage Uimp Rated Thermal Current Iu/Ith IEC 60947-3, EN 60947-3 VDE 0660 part 107 Ambient temp. +35 °C during 24 hours with peaks up to +40 °C Ambient temp. +55 °C during 24 hours with peaks up to +60 °C UL/Canada2 Rated Operational Current Ie AC-20A No-load operation IEC 60947-3, EN 60947-3 VDE 0660 part 107 690 V Occasional switching 3 phase, 3 pole 220 V-440 V under load cos ϕ 0,8 and 500 V 1 phase, 2 pole 660 V-690 V AC-21B Switching of resistive 3 phase, 3 pole 220 V-440 V loads, including mo- and 500 V derate overloads 1 phase, 2 pole 660 V-690 V Interrupting Rating UL/Canada2 600 V CSA 600 V Rated Utilization Category IEC 60947-3, EN 60947-3 VDE 0660 part 107 AC-23B Occasional switching of 3 phase 220 V-240 V motors or other high 3 pole 380 V-440 V inductive loads 500 V 660 V-690 V Short Circuit Protection Max. fuse size (aR-characteristic) Rated short-time withstand current (1s-current) Terminals for connection screw length Tightening torque of screws Min. Ambient Temperature of Stages Max. Ambient Temperature of Stages3, 4 V V V kV A A A A A A A A A A A A kW kW kW kW A A mm Nm Ib-in 690 690 690 690 690 690 690 690 690 600 600 600 600 600 600 600 600 600 on request 6 6 6 6 6 6 6 6 6 350 500 800 630 1100 1000 1450 1900 2400 350 500 750 600 950 920 1300 1700 2000 350 400 630 630 800 1000 1200 1600 2000 350 500 800 630 1100 1000 1450 1900 2400 350 500 800 500 1000 630 1200 1200 1200 350 450 500 450 630 500 800 800 800 315 350 400 360 400 400 400 400 400 250 450 500 350 630 400 800 800 800 250 400 450 315 500 350 630 630 630 200 300 350 250 350 300 350 350 350 200 300 300 200 300 200 300 200 200 200 200 200 200 200 200 200 200 200 45 75 75 45 75 45 75 75 75 90 132 132 90 132 90 132 132 132 110 132 132 110 132 110 132 132 132 55 55 65 65 65 65 65 65 65 400 500 800 630 1100 1000 2x800 2x1000 2x1250 on request Cable lug or copper bus M12 M12 M16 M16 M16 M16 M16 2xM16 4xM16 20 30 40 30 40 40 40 50 50 25 25 25 25 25 25 25 25 25 220 220 220 220 220 220 220 220 220 -5 °C (-25 °C on request) 55 °C during 24 hours with peaks up to 60 °C, permissible load see Rated Thermal Current. 47 < back to table of contents >
www.krausnaimer.comRkJQdWJsaXNoZXIy MTAxNzE=