KRAUS & NAIMER Enclosures for EMC-compliant connection
EMC-compliant connection Maintenance Switches for Maintenance Switches and Safety Switches according to IEC 60204 and VDE 0113 for EMC-compliant connection of frequency regulated motors 10 www.krausnaimer.com Contact development: 6 pole with auxiliary contacts 1NC/1NO (leading off) General Data Switch Disconnectors according to EN 60947-3 and VDE 0660 part 107 Ambient temperature (enclosed): 35 ˚C during 24 hours with peaks up to 40 ˚C Equipment Plastic enclosure, protection IP 66/67, knock-outs Handle in the OFF-position lockable with padlocks, special safety interlocked covers with enclosure With shield clips for use to continue the cable shield circuit through the enclosure Rated Data / Order Number Thermal Current I the Utilization Category AC-23 B/A, 3x400 V Breaking Capacity 3x400 V Color Handle / Backing Order Number 25 A 7,5 kW 180 A KG20B T206/D-A059 KL11V KG20B T106/D-A046 KL11V 32 A 11 kW 220 A KG32B T206/D-A054 KL11V KG32B T106/D-A040 KL11V Connection diagram Recommended tightening torque for terminal screws 1L2 1T2 1L1 1T1 1L3 1T3 2L2 2T2 2L1 2T1 2L3 2T3 13 14 21 22 PE PE KG20B 1,25 Nm KG32B 1,25 Nm External-Ø shield Insulation stripping length 12—16 9 = .. T206 .. = .. T106 .. Ø 2x25 100 190 178 93 17 Ø 25 25 A / 7,5 kW KG20B 32 A / 11 kW KG32B < Back to the table of contents >