Dimensions in mm 18 Contact development: 6 pole with auxiliary contacts 1NC/1NO (leading off) General Data Switch Disconnectors according to EN 60947-3 and VDE 0660 part 107 Ambient temperature (enclosed): 35 ˚C during 24 hours with peaks up to 40 ˚C Equipment Plastic enclosure, protection IP 66/67 Handle in the OFF-position lockable with padlocks, special safety interlocked covers with enclosure With on DIN-rails mounted clips for use to continue the cable shield circuit through the enclosure Name Art. No. Ithe AC-3 3x400V AC-23A 3x400V Handle /Color C200-4.T206/D-A001.STM 70009765 200 A 37 kW 75 kW C200-4.T106/D-A001.STM 70023125 200 A 37 kW 75 kW C316.T206/D-A050.STM 70027327 315 A 55 kW 132 kW C316.T106/D-A033.STM 70026633 315 A 55 kW 132 kW 200 A / 75 kWC200-4 315 A / 132 kWC316 C200-4 230 73 380 560 534 354 Ø 2x63 Ø 1x20 C316 280 86,5 380 560 534 354 Ø 2x72 Ø 1x20 6 POLE: 200 A / 75 kW – 315 A / 132 kW = .. T206 .. = .. T106 .. Wiring diagram 1L1 1T1 1L2 1T2 1L3 1T3 2L1 2T1 2L2 2T2 2L3 2T3 103 104 101 102 PE PE External-Ø shield C200-4 34 — 40 C316 46 — 52 < Back to the table of contents >