6 NOTES For the rating of the switch please note that the motor may have approx. 10 % higher charging rate due to the higher loss in FU-operation e.g. a motor with 7,5 kW rating the motor current has to be determined with 16,7 A instead of 15,2 A. Each Maintenance Switch has as standard 2 auxiliary contacts, 1 NC and 1 NO. Via the NO (20 ms leading) the FU can be switched off before the main contacts of the switch open. The configuration of the Maintenance Switch between FU and motor allows the use as Disconnector up to 400 Hz and as Load Switch at frequencies from 40 Hz to 100 Hz. Maintenance Switches for EMC-compliant connection of FU-regulated drives are available either with shield clips (KS- and KL-enclosure) or with clips mounted on DIN-rails (STM-enclosure). These clips are used to continue the cable shield circuit through the enclosure. Notes < Back to the table of contents >