KRAUS & NAIMER Enclosures for EMC-compliant connection

EMC-compliant connection Maintenance Switches for Maintenance Switches and Safety Switches according to IEC 60204 and VDE 0113 for EMC-compliant connection of frequency regulated motors 14 www.krausnaimer.com Contact development: 6 pole with auxiliary contacts 1NC/1NO (leading off) = .. T206 .. = .. T106 .. General Data Switch Disconnectors according to EN 60947-3 and VDE 0660 part 107 Ambient temperature (enclosed): 35 ˚C during 24 hours with peaks up to 40 ˚C Equipment Plastic enclosure, protection IP 66/67, Handle inthe OFF-position lockable with padlocks, special safety interlocked covers withenclosure with on DIN-rails mounted clips for use to continue the cable shield circuit through the enclosure Rated Data / Order Number Thermal Current I the Utilization Category AC-23 B/A, 3x400 V Breaking Capacity 3x400 V Color Handle / Backing Order Number 200 A 75 kW 1300 A C200-4 T206/D-A001 STM C200-4 T106/D-A001 STM 275 A 132 kW 2000 A C316 T206/D-A050 STM C316 T106/D-A033 STM Connection diagram Recommended tightening torque for terminal screws 1L1 1T1 1L2 1T2 1L3 1T3 2L1 2T1 2L2 2T2 2L3 2T3 103 104 101 102 PE PE C200-4  8 Nm C316  14 Nm External-Ø shield Connecting bolts C200-4 34—40 C316  46—52 C200-4 M8 C316  M12 C200-4 230 73 380 560 534 354 Ø 2x63 Ø 1x20 C316 280 86,5 380 560 534 354 Ø 2x72 Ø 1x20 200 A / 75 kW  C200-4 275 A / 132 kW  C316