KRAUS & NAIMER DC-switch with knife contacts

next ► DC-Switch with knife contacts G20S/G20

2 Table of Content G20S/G20 DC-Switch with knife contacts < For direct link click on the page number > CONTENT The most important technical data 3 Electrical data of G20S/G20 ON/OFF-Switches 4 Electrical data of G20S/G20 Change-Over Switches 5 Pre-configured Main Switches G20 6 Dimensions Pre-configured Main Switches G20 9 Dimensions G20S/G20 10

3 The most important technical data Ideal solution for DC applications G20S/G20 DC-Switch with knife contacts The most important technical data, according to IEC/EN 60947-3 Rated Insulation Voltage Ui 690 V AC Rated Insulation Voltage Ui 500 V DC Rated Insulation Voltage Ui 1000 V AC* Rated Thermal Current lu/lth 20 A * DC possible with series connection Maximum permissible wire gage mm2 AWG Single-core or stranded wire 2 x 2,5 12 Flexible wire 2 x 2,5 12 with sleeving in according with DIN 46228 2 x 2,5 – Ambient Temperature between –5 °C and +40 °C General Use G20S 150 V DC 20 A 300 V AC Pilot Duty 10 A B 300a / USA 1 IEC/EN 60204 – European standard for electrical, electronic and programmable electronic equipment and systems. 2 EN 50274 – European standard for low-voltage switchgear and controlgear assemblies for protection against electric shock and against unintentional direct contact with hazardous live parts. 3 IEC/EN 60947-3 – European standard for switches, disconnectors, switch disconnectors and fuse-combination units to be used in distribution circuits and motor circuits of which the rated voltage does not exceed 1000 V AC or 1500 V DC. The G20S and G20 switch disconnectors of the Kraus & Naimer G-series are compact, robust, and perfectly suited for direct current (DC) applications, as well as for low voltages and low currents. The G20S switches are manually operated, have a switching capacity of 1000 V/20A (DC-22A), and a high shortcircuit resistance. The directly operated G20 switches fulfill all the characteristics of a main switch according to IEC/EN 602041. The G20 switches are the ideal solution not only for DC applications but also for AC applications with high shortcircuit resistance, as well as for systems operating at low voltage and currents. In compliance with EN 502742, the IP20 finger-safe terminals prevent accidental unintentional contact with live parts. In accordance with IEC/EN 60947-33 our G20 and G20S switch disconnectors ensure the reliable operation of contacts when opening and closing. For details, please see the table on the right. Of course, the G-series can also be flexibly combined with many Kraus & Naimer extras, e. g. padlock devices.

4 G20S/G20 ON/OFF-Switches Customized contact developments are up on request. Please be so kind and advise the nominal current, voltage and utilization category as well as required terminal lugs. ELECTRICAL DATA OF ON/OFF-SWITCHES Rated Utilization Category Contacts in series Rated Operational Current le/A Permissible Voltage G20S G20 1 2 3 4 5 6 DC-21 A 60 120 180 240 300 360 20 20 110 220 330 440 550 660 20 15 160 320 480 640 800 960 20 13 250 500 750 1000 – – 20 8 330 660 990 – – – 20 6 440 880 – – – – 13 4 DC-22 A 60 120 180 240 300 360 20 20 110 220 330 440 550 660 20 7 160 320 480 640 800 960 20 4 250 500 750 1000 – – 20 2 330 660 990 – – – 10 1 440 880 – – – 5 0,5 DC-23 24 48 72 96 120 144 20 20 48 96 144 192 240 288 20 12 60 120 180 240 300 360 15 5 110 220 330 440 550 660 12 3 160 320 480 640 800 960 8 2 250 500 750 1000 – – 5 1 330 660 990 – – – 3 0,5 440 880 – – – – 1 0,25 DC-PV2 * – 500 750 1000 – – 20 – * Ratings applicable for Switch Disconnectors in Photovoltaic < Back to the table of contents > < to the dimensions > G20S/G20 ON/OFF-Switches 0-1 Switches Switch Disconnectors Pole Contacts in series G20 G20S G20 G20S Stages Name Art. no. Name Art. no. Name Art. no. Name Art. no. 1 1 G20.D101.E 70017313 G20S.D101.E 70017332 G20.TD3101.E 70095358 G20S.TD3101.E 70031783 1 1 2 G20.D201.E 70095558 G20S.D201.E 70017369 G20.TD3201.E 70095366 G20S.TD3201.E 70017384 2 1 2+1 G20.D351.E 70095564 G20S.D351.E 70095584 G20.TD3351.E 70095374 G20S.TD3351.E 70009912 3 1 3 G20.D301.E 70095568 G20S.D301.E 70095593 G20.TD3301.E 70095399 G20S.TD3301.E 70100076 3 1 4 G20.D401.E 70017328 G20S.D401.E 70017379 G20.TD3401.E 70017331 G20S.TD3401.E 70017396 4 2 1 G20.D102.E 70017314 G20S.D102.E 70017334 G20.TD3102.E 70095359 G20S.TD3102.E 70009899 2 2 2 G20.D202.E 70095559 G20S.D202.E 70017370 G20.TD3202.E 70095367 G20S.TD3202.E 70009394 4 2 2+1 G20.D352.E 70095565 G20S.D352.E 70095586 G20.TD3352.E 70095391 G20S.TD3352.E 70009913 6 2 3 G20.D302.E 70095569 G20S.D302.E 70028968 G20.TD3302.E 70095551 G20S.TD3302.E 70055212 6 2 4 G20.D402.E 70095574 G20S.D402.E 70040897 G20.TD3402.E 70095554 G20S.TD3402.E 70100078 8 3 1 G20.D103.E 70095556 G20S.D103.E 70017339 G20.TD3103.E 70095361 G20S.TD3103.E 70100079 3 3 2 G20.D203.E 70095560 G20S.D203.E 70095576 G20.TD3203.E 70095369 G20S.TD3203.E 70100080 6 3 2+1 G20.D353.E 70095566 G20S.D353.E 70095587 G20.TD3353.E 70095397 G20S.TD3353.E 70009501 9 3 3 G20.D303.E 70095570 G20S.D303.E 70095594 G20.TD3303.E 70095552 G20S.TD3303.E 70100081 9 3 4 G20.D403.E 70095575 G20S.D403.E 70095683 G20.TD3403.E 70095555 G20S.TD3403.E 70100082 12 4 1 G20.D104.E 70095557 G20S.D104.E 70017342 G20.TD3104.E 70095362 G20S.TD3104.E 70009900 4 4 2 G20.D204.E 70095561 G20S.D204.E 70095580 G20.TD3204.E 70095370 G20S.TD3204.E 70009914 8 4 2+1 G20.D354.E 70095567 G20S.D354.E 70095589 G20.TD3354.E 70095398 G20S.TD3354.E 70100083 12 4- 3 G20.D304.E 70095571 G20S.D304.E 70095595 G20.TD3304.E 70095553 G20S.TD3304.E 70100084 12 5 1 G20.D105.E 70068225 G20S.D105.E 70017346 G20.TD3105.E 70095363 G20S.TD3105.E 70100085 5 5 2 G20.D205.E 70095562 G20S.D205.E 70095581 G20.TD3205.E 70095371 G20S.TD3205.E 70100086 10 6 1 G20.D106.E 70017318 G20S.D106.E 70017348 G20.TD3106.E 70095364 G20S.TD3106.E 70009901 6 6 2 G20.D206.E 70095563 G20S.D206.E 70095583 G20.TD3206.E 70095372 G20S.TD3206.E 70009502 12

5 G20S/G20-Change-Over Switches Customized contact developments are up on request. Please be so kind and advise the nominal current, voltage and utilization category as well as required terminal lugs. Rated Utilization Category Contacts in series Rated Operational Current le/A Permissible Voltage G20S G20 1 2 3 4 5 6 DC-21 A 160 320 480 640 800 960 20 * 250 500 750 1000 – – 7 * 330 660 990 – – – 2 * 440 880 – – – – 1 * DC-22 A 110 220 330 440 550 660 20 * 160 320 480 640 800 960 8 * 250 500 750 1000 – – 3 * 330 660 990 – – – 1 * DC-23 A 48 96 144 192 240 288 20 * 60 120 180 240 300 360 15 * 110 220 330 440 550 660 6 * 160 320 480 640 800 960 3 * 250 500 750 1000 – – 1 * * Electrical data on request ELECTRICAL DATA OF CHANGE OVER SWITCHES G20S/G20 Change-Over-Switches 1-2 Switches Pole Contacts in series G20 G20S Stages Name Art. no. Name Art. no. 1 1 G20.D111.E 70017320 G20S.D111.E 70017350 1 1 2 G20.D211.E 70095684 G20S.D211.E 70017371 2 2 1 G20.D112.E 70024917 G20S.D112.E 70017352 2 2 2 G20.D212.E 70053279 G20S.D212.E 70009940 4 3 1 G20.D113.E 70017322 G20S.D113.E 70017355 3 3 2 G20.D213.E 70095685 G20S.D213.E 70017372 6 4 1 G20.D114.E 70069004 G20S.D114.E 70017357 4 G20S/G20 Change-Over-Switches with 0 position 1-0-2 Switches Switch Disconnectors Pole Contacts in series G20 G20S G20 G20S Stages Name Art. no. Name Art. no. Name Art. no. Name Art. no. 1 1 G20.D121.E 70095687 G20S.D121.E 70017361 G20.TD9121.E 70099364 G20S.TD9121.E 70017397 2 1 2 G20.D221.E 70095688 G20S.D221.E 70017374 G20.TD9221.E 70099368 G20S.TD9221.E 70095711 4 1 3 G20.D321.E 70095703 G20S.D321.E 70095709 G20.TD9321.E 70099373 G20S.TD9321.E 70048004 6 1 4 G20.D421.E 70095705 G20S.D421.E 70095712 G20.TD9421.E 70099375 G20S.TD9421.E 70048001 8 2 1 G20.D122.E 70017324 G20S.D122.E 70017363 G20.TD9122.E 70099366 G20S.TD9122.E 70069625 4 2 2 G20.D222.E 70095689 G20S.D222.E 70017375 G20.TD9222.E 70099369 G20S.TD9222.E 70062122 8 2 3 G20.D322.E 70095704 G20S.D322.E 70017378 G20.TD9322.E 70099374 G20S.TD9322.E 70048005 12 3 1 G20.D123.E 70017327 G20S.D123.E 70095708 G20.TD9123.E 70099367 G20S.TD9123.E 70017398 6 3 2 G20.D223.E 70095690 G20S.D223.E 70028281 G20.TD9223.E 70099371 G20S.TD9223.E 70025000 12 4 1 G20.D124.E 70010138 G20S.D124.E 70010139 G20.TD9124.E 70095706 G20S.TD9124.E 70010140 8 < Back to the table of contents > < to the dimensions >

6 Pre-configured Main Switches G20 PRE-CONFIGURED MAIN SWITCHES G20 Rated Utilization Category Contacts in series Permissible Voltage Rated Operational Current le/A G20 1 2 3 4 DC-23 A 24 48 72 96 20 48 96 144 192 12 60 120 180 240 5 110 220 330 440 3 160 320 480 640 2 250 500 750 1000 1 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1101/01.E 70069845 G20.TD2101/01.E 70085669 1 2 G20.TD1102/01.E 70052903 G20.TD2102/01.E 70054977 2 3 G20.TD1103/01.E 70069852 G20.TD2103/01.E 70028249 3 4 G20.TD1104/01.E 70025221 G20.TD2104/01.E 70085673 4 5 G20.TD1105/01.E 70085625 G20.TD2105/01.E 70085678 5 6 G20.TD1106/01.E 70085628 G20.TD2106/01.E 70080031 6 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1201/01.E 70085630 G20.TD2201/01.E 70085682 2 2 G20.TD1202/01.E 70085632 G20.TD2202/01.E 70085689 4 3 G20.TD1203/01.E 70085635 G20.TD2203/01.E 70085690 6 4 G20.TD1204/01.E 70071700 G20.TD2204/01.E 70071704 8 5 G20.TD1205/01.E 70085637 G20.TD2205/01.E 70085695 10 6 G20.TD1206/01.E 70071702 G20.TD2206/01.E 70085699 12 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1301/01.E 70085642 G20.TD2301/01.E 70085701 3 2 G20.TD1302/01.E 70085646 G20.TD2302/01.E 70070071 6 3 G20.TD1303/01.E 70085648 G20.TD2303/01.E 70070066 9 4 G20.TD1304/01.E 70085650 G20.TD2304/01.E 70085705 12 1 G20.TD1351/01.E 70085653 G20.TD2351/01.E 70085707 3 2 G20.TD1352/01.E 70085658 G20.TD2352/01.E 70085713 6 3 G20.TD1353/01.E 70085660 G20.TD2353/01.E 70085716 9 4 G20.TD1354/01.E 70085662 G20.TD2354/01.E 70085718 12 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1401/01.E 70071703 G20.TD2401/01.E 70085720 4 2 G20.TD1402/01.E 70085666 G20.TD2402/01.E 70085722 8 3 G20.TD1403/01.E 70085668 G20.TD2403/01.E 70071708 12 48 x 48 mm 4 Contacts in series max. 1000 V 3 Contacts in series max. 750 V 2 Contacts in series max. 500 V 1 Contacts in series max. 250 V < Back to the table of contents > < to the dimensions >

7 Pre-configured Main Switches G20 PRE-CONFIGURED MAIN SWITCHES G20 Rated Utilization Category Contacts in series Permissible Voltage Rated Operational Current le/A G20 1 2 3 4 DC-23 A 24 48 72 96 20 48 96 144 192 12 60 120 180 240 5 110 220 330 440 3 160 320 480 640 2 250 500 750 1000 1 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1101/04.FT2 70071697 G20.TD2101/04.FT2 70085670 1 2 G20.TD1102/04.FT2 70071698 G20.TD2102/04.FT2 70020764 2 3 G20.TD1103/04.FT2 70049666 G20.TD2103/04.FT2 70085672 3 4 G20.TD1104/04.FT2 70071699 G20.TD2104/04.FT2 70085674 4 5 G20.TD1105/04.FT2 70085627 G20.TD2105/04.FT2 70085680 5 6 G20.TD1106/04.FT2 70085629 G20.TD2106/04.FT2 70080113 6 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1201/04.FT2 70085631 G20.TD2201/04.FT2 70085684 2 2 G20.TD1202/04.FT2 70085633 G20.TD2202/04.FT2 70033916 4 3 G20.TD1203/04.FT2 70085636 G20.TD2203/04.FT2 70085693 6 4 G20.TD1204/04.FT2 70071701 G20.TD2204/04.FT2 70071705 8 5 G20.TD1205/04.FT2 70085639 G20.TD2205/04.FT2 70085698 10 6 G20.TD1206/04.FT2 70085640 G20.TD2206/04.FT2 70085700 12 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1301/04.FT2 70085645 G20.TD2301/04.FT2 70085702 3 2 G20.TD1302/04.FT2 70085647 G20.TD2302/04.FT2 70085703 6 3 G20.TD1303/04.FT2 70085649 G20.TD2303/04.FT2 70085704 9 4 G20.TD1304/04.FT2 70085651 G20.TD2304/04.FT2 70085706 12 1 G20.TD1351/04.FT2 70085655 G20.TD2351/04.FT2 70085708 3 2 G20.TD1352/04.FT2 70085659 G20.TD2352/04.FT2 70085714 6 3 G20.TD1353/04.FT2 70085661 G20.TD2353/04.FT2 70085717 9 4 G20.TD1354/04.FT2 70085663 G20.TD2354/04.FT2 70085719 12 Pole Name Art. no. Name Art. no. Stages 1 G20.TD1401/04.FT2 70085665 G20.TD2401/04.FT2 70085721 4 2 G20.TD1402/04.FT2 70085667 G20.TD2402/04.FT2 70071706 8 3 G20.TD1403/04.FT2 70046249 G20.TD2403/04.FT2 70085723 12 4 Contacts in series max. 1000 V 3 Contacts in series max. 750 V 2 Contacts in series max. 500 V 1 Contacts in series max. 250 V 48 x 48 mm < Back to the table of contents > < to the dimensions >

8 Pre-configured Main Switches G20 PRE-CONFIGURED MAIN SWITCHES G20 Height: 90 mm Rated Utilization Category Contacts in series Permissible Voltage Rated Operational Current le/A G20 1 2 DC-23 A 24 48 20 48 96 12 60 120 5 110 220 3 160 320 2 250 500 1 Pole Name Art. no. Name Art. no. 2 G20.TD1102/33.KS51V 70024002 G20.TD2102/33.KS51V 70023740 3 G20.TD1103/33.KS51V 70085624 G20.TD2103/33.KS51V 70009481 Pole Name Art. no. Name Art. no. 1 G20.TD1201/33.KS51V 70087829 G20.TD2201/33.KS51V 70087832 2 Contacts in series max. 500 V 1 Contacts in series max. 250 V < Back to the table of contents > < to the dimensions >

9 Dimensions DIMENSIONS PRE-CONFIGURED MAIN SWITCHES G20 Four Hole Panel Mounting – lockable handle disk G20 E Single Hole Mouting – handle with lock bar G20 FT2 Enclosure G20 KS51V 48 41,2 37,5 7 max. 4 11 5 L 8-15 5 36 48 11 45,8 7 L max. 6 41,2 37,5 5 22,3+0.4 0 +0.2 0 +0.4 0 24,1 3,2 L Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 42 53 64 75 86 97 108 119 130 141 152 163 L Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 59,8 70,8 81,8 92,8 103,8 114,8 125,8 136,8 147,8 158,8 169,8 180,8 B H 17 A Ø D2 Ø D1 9,2 Ø 64 A B D1 D2 H mm 121 86 M20/M25 M20 90 < Back to the table of contents >

10 DIMENSIONS G20S/G20 Dimensions Four Hole Panel Mounting G20S/G20 FT16 Single Hole Mounting G20S/G20 FT2 48 +0.4 0 +0.2 0 +0.4 0 24,1 3,2 22,3 11 L 7 max. 6 41,2 37,5 5 48 36 41,2 37,5 7 L max. 5 11 5 +0.2 0 16,2 +0.2 0 12 Ø 36 27 5,9 L G20S Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 63,8 74,8 85,8 96,8 107,8 118,8 129,8 140,8 151,8 162,8 173,8 184,8 L G20 Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 46,5 57,5 68,5 79,5 90,5 101,5 112,5 123,5 134,5 145,5 156,5 167,5 L G20S Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 77,3 88,3 99,3 110,3 121,3 132,3 143,3 154,3 165,3 176,3 187,3 198,3 L G20 Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 59,8 70,8 81,8 92,8 103,8 114,8 125,8 136,8 147,8 158,8 169,8 180,8 < Back to the table of contents >

11 DIMENSIONS G20S/G20 Dimensions Four Hole Panel Mounting G20S/G20 E Base Mounting – Four Hole Mounting G20S/G20 VE 64 36 8-15 5 7,5 41,2 L Ø 4,1 48 11 7 2,5 37,5 max.10,5 48 41,2 37,5 7 max. 4 L 11 5 8-15 5 36 L G20S Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 59,3 70,3 81,3 92,3 103,3 114,3 125,3 136,3 147,3 158,3 169,3 180,3 L G20 Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 42 53 64 75 86 97 108 119 130 141 152 163 L G20S Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 62 73 84 95 106 117 128 139 150 161 172 183 L G20 Stages 1 2 3 4 5 6 7 8 9 10 11 12 mm 44,5 55,5 66,5 77,5 88,5 99,5 110,5 121,5 132,5 143,5 154,5 165,5 < Back to the table of contents >

www.krausnaimer.com © Kraus & Naimer, October 2024