DC-side disconnectors for photovoltaic power supply systems in accordance with IEC 60364-712 8 Data valid only if the pre-assembled bridges have not been modified. * Valid for ungrounded or midpoint-grounded PV grids, overvoltage category III, pollution degree III 70 34 184 80 76,2 5 34 + + – – Input Output Input 44,5 47,5 69,5 22,5 5,2 90 45 General Data Switch disconnectors in accordance with EN 60947-3, VDE 0660 part 107 Utilization category for photovoltaic applications: DC-PV0 Opening and closing a PV circuit to disconnect when no current is flowing DC-21B Switching of resistive loads, including moderate overloads Ambient temperature (open): 50 °C over 24 hours with peaks of up to 55 °C Finger-safe terminals in accordance with VDE 0660-514 and DGUV V3 Maximum conductor cross section (use only copper conductors) single wire or stranded wire flexible wire without / with wire-end ferrules (according to DIN 46228) 50 mm² 35 mm² Mounting DIN rail mounting with screw and quick mounting in accordance with EN 60715 Faceplate for 45 mm standard cutout, F-handle black Name Art. No. Ue Ie DC-PV0 Ie DC-21B Max. UL PV Ui * KG80.T308/P1.VE2 70040670 800 V DC 60 A 60 A 1000 V DC 1000 V Wiring diagram Twist torque for clamping screws Stripped length KG80 3,00 Nm KG80 14 N 2T1 N 1T3 Input Output + – + – Switching program: 2-pole, 8 contacts per circuit (2 x 4 in series) 800 V DC : 60 A 1 x 2-pole 800 V DC
RkJQdWJsaXNoZXIy MTAxNzE=